Over the last fifteen years we have seen solar panels and wind turbines
slowly make their way into the mainstream, and more recently heat pumps have had
growing interest, however the bottom line has always been that fossil fuel
technologies are cheaper to install than renewables, and far more capable of
satisfying a properties demand for energy, and when compared to renewable fuels
such as wood or biomass are also cheaper to run. That is until recently,
with oil, gas, and electricity prices now soaring, the pressure to find
alternative cheaper sources of heat is driving a huge increase in demand for
wood burning systems. 
At DPS we have been designing thermal storage systems to run using multiple
fuel sources for over fifteen years, and in the last year we have seen the
popularity of wood systems go through the roof, with most customers are now
asking that their hot water systems are supplied with suitable connections for
wood burning stoves or cookers, even if only for 'future-proofing' their
systems.
With the growing demand we are also seeing a rise in the number
of systems that have been installed dangerously, and without a though for the
safety measures that must be followed when using a fuel that cannot be turned
off with the flick of a switch. In this guide we wish to clarify the basic
restrictions that must be considered when designing a wood burning system, and
to cover the methods we employ to design a fully integrated and safe system,
while still following the cardinal rules...
-
A wood burner must be part of a vented water system,
with an uninterrupted path to atmosphere.
-
The system must ensure all heat generated to water is
removed from the heater (and system) without reliance upon electrical power,
the operation of pumps or human intervention. i.e. the system water
must not reach
100°C under any circumstances.
Click here to
see Case Study
The Basic Principles of the Heat Bank Thermal Store...
With a modern Heat Bank Thermal Store from DPS the following are all
possible...
-
A wood burner can be used to drive central heating including
radiators, underfloor heating, with both vented and pressurised heating
circuits.
-
A wood burner can generate mains pressure hot water taps and
showers.
-
A wood burner can be combined with a gas or oil boiler,
electric elements, heat pump, solar panels and other biomass boiler or wood
burner to form a true multi-fuel heating system.
This is all possible because of the unique way that a Heat Bank Thermal Store
works, far different to a traditional or unvented hot water cylinder. The
key difference is that the stored water is not the same water that comes out of
taps. In fact the stored water is the same water that fills the wood
burner, and central heating system. The domestic hot water that feeds taps
is heated up as it is drawn, using the heat stored in the Heat Bank Thermal Store as a
battery, and using a Plate Heat Exchanger to transfer the heat as it is
needed.
The diagram below shows a simple system with a wood burner
heating the store, which in turn heats radiators, under-floor heating and mains
hot water to taps. The
system if fully vented, with a feed and expansion tank used to fill the system,
keep it topped up, and to take up expansion of the water in the system.
The system shown is however incomplete as we have not shown a
form of overheat protection or dump to get rid of excess heat. Before we
cover this part of the design it is best to go over the basics of the wood
burners and the level of protection required.
Types of Wood Burner...
There are hundreds o models of Wood burners on the market, however they can
generally be sorted into one of four categories:
-
Room Heaters, where the burner is not connected to a water system,
and the heat given off is used to heat the room it stands in. At DPS we are
not interested in pure room heaters - they are not connected to a water
system or a thermal store and as such there is no further design needed
other than ensuring the flue in installed correctly.
-
Basic Room and Water
Heaters (boiler models), where a percentage of the heat
generated goes into the room, and the rest goes into heating water for
driving central heating or generating hot water for taps. The burn rate of
these systems is manually controlled by opening or closing the air intake to
increase or decrease the intensity of the fire. These are the 'most
demanding' to the designer as one must be able to ensure that the maximum
amount of heat that can be given off from the burner is carried away from
the stove to prevent water in it boiling, and can be stored or dumped
somewhere safely (even during a power cut).
-
Thermostatic Room and Water Heaters, are the same as above but
also has the facility to shut down the air intake rate automatically when
the temperatures get too high. This takes a little pressure off the designer
as it limits the amount of heat that must be stored or dumped somewhere
safely to prevent water in the system from boiling. 
-
Pellet
Boilers, which are electrically controlled and burn pellets (as opposed
to logs). These devices are highly controllable and can turn
themselves off safely when no further heat is required, and as such are easy
to design for as there is no need for additional overheat protections.
To ensure that you are fully aware of what type of wood burner you have and
what precautions must be taken, the following questions should be put to the
manufacturer of the heater you intend to use:
-
What is the maximum output to water (in kW) from the heater when
fully loaded ?
-
What is the maximum output to the room (in kW) from the heater
when fully loaded ?
-
Does the heater automatically shut down its rate of burn at higher
temperatures ? If yes then what is the output (in kW) to water that
needs to be dumped at this lower burn rate?
When selecting a wood burner it is also important to ensure that the room
output is matched to the heating requirements of the room in which it is placed,
and not oversized. This is important in boiler models as the room can get
uncomfortably hot while insufficient heat is provided to water for use in
heating the rest of the property. On thermostatic models one may find that if
they are oversized for the room they are in that the heater will shut down the
burn rate and again provide insufficient heat to water for the rest of the
property. To overcome these problems make sure that the output to water is
relatively high when compared to the room output... one can always have a
radiator in the same room as the wood burner to top up the heat in that room if
required. Another solution is to install ducting for circulation of warm
air around the property, and to move heat from the primary room into adjacent
rooms.
Sizing a Heat Bank Thermal Store...
As the Heat Bank Thermal Store is used to store and distribute heat energy,
the size of store used is dependent upon how much heat you want to store.
There are a few factors that influence this...
-
Total amount of heat (in kWh) that the wood burner generates
in a full load.
-
Peak hot water demand.
-
Size of gas or oil boiler (in kW) connected to store as a
backup.
Working out the total amount of heat generated depends of types of fuel, how densely
it is packed, the efficiency of the burner, and how much of the energy goes to
water rather than to the room If one follows typical assumptions regarding
wood type, 60% loading of the wood burner by volume, and 80% efficiency, then
the following rule of thumb can be used to estimate the volume of thermal
storage that is needed to take a full burn (for the full calculation and
assumptions used, please see appendix 1) from a known combustion chamber size
filled with logs.
Volume of storage required (litres) = Length (cm) x
Width (cm) x Height (cm) x 0.017
It is not always required to store a full burn as it is fairly
common for the central heating to be running at the same time as the burner is
alight. If this is the case then the store size can be reduced.
To help with other common calculations regarding the size of
store required to take a charge, or how long a certain size of store will run
central heating for before it goes cold, we have created our EnergyStorage
Calculator, which can be accessed or downloaded free of charge from
the Flash
Tools page on the DPS website, www.heatweb.com
There is also a useful Cylinder
Size Calculator to work out the dimensions of stores for
various storage capacities and store diameters that are available from DPS.
One
must not forget that the size of thermal store also depends on the total volume
of hot water required between store reheats. A cylinder that is required
to deliver five full baths of hot water within a half hour period will need to
be much larger than one that is only required to deliver one shower.
Again, to take the donkey work out of the calculations we have provided our WaterLoad
Calculator which allows accurate sizing based on your
selection of hot water loads, as well as providing adjustment for an additional
boiler input.
We use these tools daily in the designing and sizing of Heat Bank Thermal Store systems, and
please feel free to make use of these and all the other tools on our Flash
Tools page.
Circulation and Pipework...
Making sure there is suitable circulation of water to prevent it from boiling
in a wood burning system is probably the greatest challenge to the system
designer. Armed with a figure for how much energy is generated to water by
your chosen heater, one can then proceed to plan out the pipework layout that
will be the key to making things work, and the first principle that needs to be
understood is that of gravity circulation, or thermo-siphon.
Quite simply this is the way that heat rises relative to cold, and is the only
way to ensure circulation of hot water without the use of pumps.
The forces generated by thermo-siphon are small, nothing like the power of a
pump, so it is important to size pipework larger than one would for a typical
boiler installation in order to reduce the resistance to flow. 28mm
pipework is fairly standard, however larger sizes may be necessary for higher
output heaters. Pipework should also rise (and fall) continuously, with
air locks to be avoided at all costs, and horizontal runs kept to a minimum as
they will reduce the output that can be transferred.
If it is required to connect to a thermal store on the same level as the wood burner
then it will generally be necessary to connect a gravity circuit to radiators
upstairs, as well as a pumped circuit to move the heat to loads on the same
floor. There is no problem installing pumps on a wood burner system provided
there is also a gravity circuit that can take away the full output of the burner
in the case of a pump failure or power cut. The diagram below shows one
possible configuration.

Overheat Protection on Heat
Bank Thermal Stores...
Sometimes it is simply not possible to install heat dump
radiators that can remove all the generated heat using gravity
circulation. In these circumstances DPS can offer alternative forms of
overheat protection on Heat Bank Thermal Stores to guard against boiling of water in the
system. It is still a requirement to transfer the heat to the thermal
store via gravity, but the store can then provide the dumping facility for
excess heat when the store starts getting too hot.
There are two levels of protection that we use on a Heat
Bank Thermal Store to remove heat. The first requires power to be present and works by
turning on the central heating pump to get rid of heat when a thermostat on
the store reaches a preset temperature, typically 90°C.

The second uses a coil fitted inside the Heat Bank Thermal Store, through which we pass
cold mains water that then heats up (and cools the store as it does so)
before being discharged to drain. A mechanical valve (approved for
this purpose) initiates the flow of mains water when the store reaches
95°C, and requires no power to be present. This form of overheat
protection is capable of removing over 30kW of heat from the store, and it
suitable for the largest domestic wood burners. More information on
the discharge valve can be found in appendix 2.
The two forms of protection are typically used together so
that the central heating is used as an automatic dump under normal
circumstances, but in the event of a power cut of pump failure the discharge
to drain comes into play.
Overheat Protection using a Plate Heat Exchanger...
It is possible to build overheat protection into a pumped
wood burner system by using a plate heat exchanger in place of dump
radiators. They do the same job as a radiator - removing heat from the
system - except the heat is transferred to cold mains water, rather than to
air. The plate heat exchanger has one big advantage in been able to
dump huge amounts of energy - far more than radiators are capable of.
The following diagram shows a suitable circuit which allows
both pumped operation to a thermal store, and also has a gravity circuit
that comes into play when the pump is not running. During overheat
conditions the TS130 valve opens up to allow the cold mains to flow through
the heat exchanger, cooling the circuit and driving gravity
circulation. This form of overheat works without power, although power
will required to pump water from the store to provide central heating.

 The
circuit shows the use of two other components that are extremely useful in
designing circuits for wood burners, the Acaso Termovar and Termobac
valves. The Termovar is a temperature control valve that mixes two
water inputs (hot/cold) to achieve a target temperature. It is most
useful for ensuring that the temperature of the water in the wood burner
circuit is brought up to a minimum temperature to improve combustion and
prevent 'smoking' flues. The Termobac is a non-return valve with a swing
gate that provides a route for gravity circulation. It is used to connect to
gravity circuits that should only come into play when required.
 |
DPS can supply a pre-fabricated overheat
assembly for pumped wood burner systems that incorporates pump,
temperature control, plate heat exchanger and overheat discharge
valve, as well as a backflow preventer that allows the swing from
pumped to gravity. |
Multi-Fuel Systems...
One of the main advantages of a Heat Bank Thermal Store is the ability to
combine numerous heat sources in a system, allowing the end-user to choose
what fuel to use. Typical heat sources that are connected are...
Wood
burners
Gas or oil boilers
(vented or pressurised system boilers)
Solar panels
Heat pumps
Electric elements
(powered from mains supply, or from wind turbines)
Central boiler plants
on a communal system
The following diagrams show how connection of various heat
sources is possible. All these schematics have been generated using
our online Schematic
Designer, available on our web site for anyone to use.
|
Connection to a Heat Pump
Direct Connection

|
Electric Heating
From 3kW to 15kW

|
Complete Multifuel System using Wood Burner, Gas Boiler, Solar
Panels, & Electric Backup
Driving Mains Pressure Hot Water,
Underfloor Heating on Ground Floor, Radiators Upstairs.
 |

3D Models of a complete system can
also be found on our web site at www.heatweb.com/3d
These are in 3D PDF format and can be
viewed, rotated, and zoomed in on using the free Adobe reader. |
Multifuel Heat Bank Thermal Store Design
CXC-290-DBADD-CIMZH+OHCOIL+STAT...
This is an example of the final DPS Heat
Bank Thermal Store, embodying the aforementioned multi-fuel heating system in a fully
pre-fabricated, wired and tested product.
GX Recovery System, Solar
Coil, Solid Fuel Connections (28mm), CB18-40 Plate Heat Exchanger (up to
55lpm), Themostatic Mixer: Heatguard 28mm, 28mm GX Primary Valve, Twin
Cylinder Thermostats (Buffer), Economy Mode Cylinder Thermostat, Boiler
Pump:Standard 6m, 22mm Htg Circuit (Upper Store), Standard 6m Head Pump (Upper
Store), 28mm Htg Circuit (Lower Store), Underfloor Heating Temperature
Control, 28mm, Standard 6m Head Pump, Two Channel Programmer (Ht+Htg), TP7000
Programmable Room Thermostat, 3kW Immersion Heater (Half Store), Overheat to
Heating, Overheat to Drain via Finned Coil, Temperature Gauge.
 |
 |
1 Plate Heat Exchanger, CB18-30 (145kW)
2 Flow switch
3 Heat Exchanger Pump
4 Thermostatic mixing valve, 28mm
5 Drain off cock
7 White plastic coated steel casing
8 Vent
9 Cold Feed
11 Wiring Centre
13 Boost Immersion Heater
17 Cylinder Thermostat, Immersed [70°C]
28 Danfoss TS715 Programmer (Hot Water)
30 Danfoss TP7000 Programmable Thermostat
32 Flow to Solar Coil
33 Return from Solar Coil
34 Solar Sensor Pocket
35 Overheat Relief Regulating Valve
36 Overheat Relief Discharge Valve
40 Primary Return Valve, 28mm
42 Heating Pump 5m
44 Heating Pump 6m
48 Temperature Gauge
53 Y-Pattern Strainer
55 Solid Fuel / Gravity 1'' Connection
74 Economy Mode Cylinder Thermostat
75 Finned Coil (Overheat) |

This design can be generated using our PANEX
Heat Bank Thermal Store Designer, available to use on our web site, as well as almost
any combination of the systems talked about. The tool includes a wizard to
help automatically select a design. A design code is generated and
this makes it easy for us to bring up any designs our customers show an interest
in, check the designs, provide further technical consultancy, and generate
quotations.
Connecting a Wood Burner to a Sealed Heating
System...
Something that is often asked is how do you connect a vented
wood burner to drive a pressurised central heating circuit ? This is
easily achievable with a Heat Bank Thermal Store using a plate heat exchanger to transfer heat
from the vented store into the pressurised heating circuit. The diagram
below left shows this, and also shows how a system boiler can be brought
into the equation. Running a pressurised heating circuit from the
store also allows radiators to be sited higher than the feed and expansion
tank, and this is sometimes necessary if the feed and expansion tank cannot
be sited at the highest point in the system.
 |
Smaller central heating loads can be drive through a
coil, rather than a plate heat exchanger.

|
The
Heat Bank Thermal Store and The Zero-Carbon House...
At Ecobuild 2008 we were invited to participate as part of the
Zero Carbon House by Zedfactory and Bill Dunster
Architects, a full-size installation, stripped back to reveal the anatomy of
the building, the design features, products and solutions which combine to make
zero carbon housing a reality now. Visitors were able to tour the entire
structure and learn about the materials used, its systems and energy performance
as well as the pre-fabricated timber frame panels that made it possible to
complete the entire structure in just three days ready for the exhibition!
DPS has worked closely with ZedFactory to provide the
ZedStore... not just a hot water cylinder, but rather the centre of the house's
energy system. The ZedStore has been designed to work in conjunction with a
centralised wood chip boiler, feeding typically six properties on a communal
circuit, as well as wood burners and solar panels fitted in each of the
properties, and demonstrates how wood burning technologies can be combined with
other renewable heat sources to form a basis for zero-carbon
design.
"It
is all very well having all this zero carbon heat if it then has nowhere to
go. For many years this has held back the harvest possible from solar thermal
and biomass and hence payback. Forming a partnership with DPS we found a
like-minded manufacturer able to design heat stores to make the most of the
renewable technologies we have sourced." ZedFabric Innovations
Read
about The Beddington Zero Energy Development, or BedZED, the UK’s largest
eco-village, by Zedfactory.
Using the following information (from the Solid Fuel
Association) it is possible to calculate the total amount of heat generated
from a wood burner, provided you know the internal dimensions of the burner
for loading wood. This is important if the plan is to store up the
heat given off by a full load of wood, possibly on an overnight burn for
running central heating in the morning before the wood burner is reloaded.
| |
|
Weight
per
m3 in kg |
Gross
heat value
kWh/kg (btu/lb) |
%
Moisture
when green |
Seasoning
time
in summers |
|
Hardwoods
(fully air dried)
|
Ash |
674 |
4.1
(6,350) |
35 |
1 |
| Beech |
690 |
4.3
(6,700) |
45 |
1-2 |
| |
Birch |
662 |
4.1
(6,350) |
45 |
1 |
| |
Elm |
540 |
3.6
(5,600) |
60 |
2-3 |
| |
Oak |
770 |
4.5
(7,000) |
50 |
2-3 |
| |
Poplar |
465 |
2.6
(4,100) |
65 |
1 |
|
Softwoods
|
Pine/Fir |
410 |
2.6
(4,100) |
60 |
1 |
As an example, if the internal dimensions of the wood burner are 500mm x 250mm x
250mm then the volume of the space is calculated as follows...
Volume (m3) = Length (m) x Width (m) x
Height (m) = 0.5 x 0.25 x 0.25 =
0.03125 m3
To get the maximum load weight, multiply this figure by the
density values in column 1 (Weight per m3) for your wood type ... we will
assume Ash...
Max Weight (Kg) = Volume (m3) x Density
(Kg/m3) = 0.03125 x 674 = 21 Kg
As logs cannot be perfectly packed (as some briquettes can)
multiply by 60/100 (for 60% by volume)...
Max Weight of Logs (Kg) =
(60 / 100) x 21 = 12.6 Kg
Next, to work out the energy given off, multiply this figure
by the value in Column 2 (Gross heat value) for your wood type...
Gross Output (kWh) = Weight
(Kg) x Gross Heat Value (kWh/Kg) = 12.6
x 4.1 = 51.8 kWh
To work out the Net heat output, multiply this further by
the efficiency figure quoted for your wood burner... lets assume 80%
efficiency...
Net heat value (kWh) = Gross output (Kw)
x Efficiency = 51.8 kWh x (80 / 100) = 41.45
kWh
Next, divide this by the percentage of heat that goes to
water (rather than to room)...
lets assume 60% ...
Net heat output to water from a full
load = 41.45 x (60 / 100)
= 24.9 kWh
To convert this figure into a suitable volume of stored
water, assumed to be heated through a 40°C rise for a typical thermal
store, multiply the net heat output by 860 and divide by the
temperature rise to give...
Volume of storage required (litres)
= Output (kWh) x 860 / 40 = 24.9
x 21.5 = 535 litres
If one follows similar assumptions regarding wood type, 60% loading by
volume, 80% efficiency then this can be simplified to the following rule of
thumb...
Volume of storage required (litres) = Length
(cm) x Width (cm) x Height (cm) x 0.017
Appendix 2. Overheat Relief Valve, Honeywell
TS130.
Application
The TS130 Temperature Relief Valve for heating systems to
DIN 4751, Sheet 2 is a self-acting valve which is activated by
the flow temperature of the heat generator. It opens and discharges
water from the heat generator or condensing coil at a
flow temperature of 95°C (203°F) and thereby prevents a
significant temperature rise in the heat generator.
Features
• Construction tested to DIN 3440
• Immersion pocket with double heat sensors
• With test facility
• Capillary tube protected against kinking by steel sheath
• Immersion pocket with external thread
Function
The temperature relief valve is actuated by the flow temperature
of the heat generator. It comprises a spring-loaded
valve and a bellows operated temperature sensor. When a
boiler flow temperature of 95ºC is reached the force exerted
by the bellows system becomes greater than the force of the
spring and the valve opens. Heated potable water then flows
out and this is replaced by cold water from the supply network.
This absorbs excess heat from the heat generator and
prevents overheating.
Specifications
Heating system capacity max. 93 kW (80 000 kcal/h)
Operating temperature 95°C (203°F)
Flow capacity 2000 kg /h water at a minimum
flow pressure of 1,0 bar (14,5 P.S.I.)
Connection size Rp 3/4" (DIN 2999) |
Design
The Temperature Relief Valve comprises:
• Housing with internal thread
• Bonnet
• Valve piston with seal disc
• Spring
• Immersion pocket
• Remote double temperature sensor with capillary tube
• Immersion sensor G 1/2” (ISO 228)
Materials
• Brass housing, bonnet and immersion pocket
• Copper temperature sensor
• Copper capillary tube
• Brass valve piston
• Hot-water-resistant elastomer seals
|
Appendix 3. Approximate Running Costs of Various
Fuels.
The following table has been composed on 14 November 2008 and compares the
costs of various fuels when used for heating. We have approximated boiler
efficiencies and used readily available suppliers for our comparisons.
|
Cost
pence/kWh |
|
| Wood |
2.7 |
From
Surrey Logs (www.andrewheard.co.uk) |
| Gas |
4.0 |
From
Energy Comparison Web Site |
| Oil |
4.7 |
From
Southern Counties Fuel 42.97p/ltr |
| Cheap
Rate Electricity |
5.2 |
From
Energy Comparison Web Site |
| Peak
Rate Electricity |
10.9 |
From
Energy Comparison Web Site |
Appendix 4. Wood Suppliers.
Article on how Croydon Council is making locally sources renewable heating via
wood a reality for communities... http://www.grownupgreen.org.uk/library/?id=880
The following links can be found at http://www.carbonneutralfuel.com/logs.html
| UK Mainland |
RWS Bio Fuels |
Wood Pellets, Sawdust logs and Bio Bricks |
| North England |
Bingley Logs |
Logs delivered in Cheshire, Cumbria, Derbyshire, Lancashire,
Merseyside, North East, Yorkshire
|
| North West England |
Grange Wood
Fuels |
Seasoned hardwood logs in nets, bags or bulk loads |
| Lincolnshire, Market Rasen |
Lincolnshire
Tree Services |
Seasoned hardwood logs delivered |
| Nottinghamshire & Lincolnshire |
logs2buy.com |
Bagged hardwood logs with a free friendly delivery service Newark,
Nottingham and Lincoln areas. |
| Surrey, Shalford |
Surrey Logs |
Logs and kindling - collect or delivered |
| Sussex, Worthing |
Sussex
Logs |
A mix of ash, oak and beech logs in full or half loads |
| West Lothian, Linlithgow |
Champfleurie
Estate |
Bags of seasoned logs delivered |
Appendix 5. Thermo-Siphon Calculations.
The following data may help in calculating the forces generated through
thermo-siphon (gravity) action.
|
Temp
( °C )
|
Density
tap water
( g/cm3 )
|
|
4
|
0.99999
|
|
20
|
0.99823
|
|
40
|
0.99225
|
|
60
|
0.98389
|
|
80
|
0.97487
|
|
Pressure of Water = height x 9.81 x density
With a temperature rise from 60°C to 80°...
Difference in Pressure between hot and cold = height
x 9.81 x ( 983.89 - 974.87 )
= height (m) x 88.4862 (i N/m2)
= height (m) x 0.009023061 (metres head
of water)
This force needs to balance out with the pressure losses in the
pipework under circulation.
|
|