Heat Bank Thermal Store System Stowaway advanced F+E 28 Plate Heat Exchanger (45+ ltr/min) Indirect 40mm Foam Insulation High duty primary coil Y-Plan primary controls Fitted programmer All fitted controls are wired Manual Fill - No Overflow 28mm Primaries Backup Immersion Heater Low Water Level Indicator PCB Wiring Centre Cased
1 Integral Expansion Vessel (Unpressurised) |
|
||||||||||
The unit is fitted with an Integral Overflow Chamber [8], which traps small volumes of water discharged as a result of overfilling. Water in the chamber can be drained off via the Overfill Drain Cock [66]. The unit MUST be watched during filling as excessive overfilling will result in over-spill onto the floor. |
The unit is fitted with two heat exchangers, and is capable of delivering 45 litres/minute @45°C (80°C storage). |
A Mains Water Isolating Lever Valve must be fitted within the cylinder cupboard, in clear view and easily accessible. A Strainer (supplied loose) must also be fitted, down stream of the isolating valve, to protect the flow switch [4]. |
It is advised that the mains water is tested for hardness. In areas of hard water, we advise the use of a scale inhibitor. |
It is important that SENTINEL X100 Inhibitor is used to protect the Heat Bank Thermal Store. Use 1 litre per 100 litres of stored water. A suitable anti-freeze, such as X500, should also be added when there is a chance that the unit will be left filled and unheated in freezing conditions. |