Pandora Heat Bank Thermal Store
General Technical Specifications
  

System Classification Unpressurised Thermal Store with Plate Heat Exchanger
Maximum Mains Pressure 6 Bar Continuous, 9 Bar Peak
Minimum Mains Pressure 0.5 Bar
Hot Water Supply Temperature 35-65°C User Set, Lockable
Heatguard (Reliance Water Controls) 22mm or 28mm
Plate Heat Exchanger Output
to Hot Water
Type 1:  100 kW
Type 2:  160 kW
Type 3:  320 kW
Heat Exchanger Material Stainless Steel, Copper Brazed
Heat Exchanger Test Pressure      76 Bar
Operating Store Pressure Atmospheric (No pressure)
Storage Temperature 70 to 80°C
Store Construction Material Stainless Steel or Copper
Casing Material Plastic Coated Steel
Insulation 40mm CFC Free Polyurethane
50mm on Stores 500mm+
Other on application
Discharge Pipe None required. 
Store is Vented and Manually Filled, with no connection between Mains and Store (only to external heat exchanger).
Power Supplies 3A Fused Spur for Controls
+  Immersion Heater Supplies (16A)
Servicing Requirements 1 litre Corrosion Inhibitor added every 5 years.
Initial quantity is factory added into store before dispatch.
Guarantees 20 years on Store
2 years on Components
1 year On-Site Backup (9am-5pm weekdays)

 

More on the Pandora...