MCZ Hydro Stoves - A16 alarm

Solution

There have been instances reported of a A16 alarm being raised on the MCZ Hydro stoves (Musa, Ego, Suite, Star) with the description "Water Overpressure Alarm" or "Manostat". This can occur when enabling some technical parameters on the older versions of the stove.

The alarm relates to a sensor that is not present on this range of stoves and is therefore raised in error. It can be cleared by undertaking the following steps:

 

  • Press and hold the Escape button (upper left of display panel) until alarm clears - approx 5 seconds.
  • Enter the Technical Menu. Select "Mano Set" and change it to Off.
  • The A16 alarm will now be activated again. Press and hold the On/Off button on the control panel until the alarm clears and the display reads 'Check' - approx 5 seconds.

The alarm is now cleared.

 